STANDARDS & FORMULAS

Cable Tray

Cable tray routed along your lines and sized from the real cables it carries, with its sections.

Standards and regulations

  • IEC 60364-5-52
    Low-voltage installations - wiring systems

    The default: one layer, a diameter’s gap between neighbours (reference method F: the cables keep their full rating).

  • NEC 392.22
    Cable trays - number of conductors (fill)

    The “by area” option: the cables’ areas within a percentage of the tray’s (50 % by default).

Formulas

Width (one layer, a diameter apart)

W = (Σ D + Σ gaps) × (1 + spare) → the next standard width

  • D = each cable’s outer diameter
  • gaps = one diameter between neighbours (the smaller cables’)
  • spare = 25 % by default; never under the minimum width

Width (by area)

W = Σ (π D² / 4) / (H × fill limit)

  • H = the tray’s height

Fill

by width = Σ D / W · by area = Σ (π D² / 4) / (W × H)

Design rules it applies

  • The width drops by itself after each branch
  • Dipped under the beams it would hit

For reference. MO.tool works these out to help your design; the engineer remains responsible for it. Always check the edition of each standard your project uses and the requirements of the local authority (DEWA, ADDC, Civil Defence…).

Back to Cable Tray