Reactive power to correct
Qc = P × (tan φ1 − tan φ2)
- P = the board’s load (kW)
- φ1 = the power factor now (0.8 as a rule)
- φ2 = the power factor wanted
A board’s capacitor bank (power factor correction) sized from its loads and put on its schedule and single line.
The breaker and cable sized for 1.43 × In.
The bank in equal steps (APFC panel, standard or detuned).
The power factor wanted: 0.90 lagging at least, 0.95 recommended (DEWA).
Qc = P × (tan φ1 − tan φ2)
In = Qc / (√3 × U)
sized for 1.43 × In
For reference. MO.tool works these out to help your design; the engineer remains responsible for it. Always check the edition of each standard your project uses and the requirements of the local authority (DEWA, ADDC, Civil Defence…).