Loop resistance (out and back)
R = 2 × L × r / 1000 + Σ R(isolators)
- L = the loop’s cable length (m), as drawn, with the riser
- r = the core’s resistance (Ω/km, IEC 60228): 1.0 mm² 18.1 · 1.5 mm² 12.1 · 2.5 mm² 7.41
FA Riser Diagram works with Fire Alarm: they share these references. Fire alarm loops: wiring, numbering, the loop’s DC voltage drop check and the riser diagram.
Detector spacing, manual call points, notification appliances and installation notes.
The BS option of the installation details and notes.
The copper core resistance (Ω/km at 20 °C) for the loop and 100 V line checks.
R = 2 × L × r / 1000 + Σ R(isolators)
V(device) = V(panel) − Σ I(alarm) × R(cable up to it)
For reference. MO.tool works these out to help your design; the engineer remains responsible for it. Always check the edition of each standard your project uses and the requirements of the local authority (DEWA, ADDC, Civil Defence…).