STANDARDS & FORMULAS

FA Wiring

FA Wiring works with Fire Alarm: they share these references. Fire alarm loops: wiring, numbering, the loop’s DC voltage drop check and the riser diagram.

Standards and regulations

  • NFPA 72
    National Fire Alarm and Signaling Code

    Detector spacing, manual call points, notification appliances and installation notes.

  • BS 5839-1
    Fire detection and fire alarm systems for buildings (non-domestic premises)

    The BS option of the installation details and notes.

  • IEC 60228
    Conductors of insulated cables

    The copper core resistance (Ω/km at 20 °C) for the loop and 100 V line checks.

Formulas

Loop resistance (out and back)

R = 2 × L × r / 1000 + Σ R(isolators)

  • L = the loop’s cable length (m), as drawn, with the riser
  • r = the core’s resistance (Ω/km, IEC 60228): 1.0 mm² 18.1 · 1.5 mm² 12.1 · 2.5 mm² 7.41

Voltage at each device

V(device) = V(panel) − Σ I(alarm) × R(cable up to it)

  • I(alarm) = each device’s current in alarm (detector quiescent, sounder / beacon alarm current)
  • Checked against the lowest voltage the device works on (17 V as standard)
  • Class A: worked out fed from one end (a break by the panel) and from both ends

Design rules it applies

  • Numbering in the loop’s order: FACP-1/SD/01, FACP-1/HD/01 …, written into FA Address
  • Class A loops drawn back to the panel
  • Riser diagram per panel, drawn from the loops: every floor, every device with its number, isolators and the legend

For reference. MO.tool works these out to help your design; the engineer remains responsible for it. Always check the edition of each standard your project uses and the requirements of the local authority (DEWA, ADDC, Civil Defence…).