STANDARDS & FORMULAS

Generator Sizing

The generator for the emergency loads you tick, sized step by step; the biggest step decides.

Standards and regulations

  • ISO 8528-1
    Generating sets - application, ratings and performance

    The kinds of rating (ESP, PRP, LTP, COP), the 0.8 power factor and the 70 % average load.

  • IEEE 446
    Emergency and standby power systems (Orange Book)

    The voltage dip when the largest motor starts.

  • NFPA 20
    Stationary fire pumps

    A fire pump’s controller dips 15 % at most as it starts.

Formulas

1 · Running load

P = Σ P(demand) × diversity · S = P / pf · R1 = max(P / 0.8, S) × (1 + spare)

2 · Non-linear loads (UPS, drives)

R2 = (max(P / 0.8, S) + (k − 1) × S(non-linear)) × (1 + spare)

  • k = how many times the non-linear kVA is counted

3 · Largest motor start (voltage dip)

R3 = S(start) × X′d × (1 − ΔV) / ΔV

  • S(start) = the motor’s running kVA × its starting multiple (DOL, star-delta, soft starter, VFD)
  • X′d = the alternator’s transient reactance (0.15 – 0.25 as a rule)
  • ΔV = the dip allowed (15 – 20 % as a rule)

4 · Engine while the motor starts

R4 = (P − P(motor) + S(start) × pf(start)) / 0.8

5 · Average load (ESP / PRP)

R5 = P × load factor / (0.70 × 0.8)

Site derating and the set

Required kVA = max(R1 … R5) / (Ft × Fa) → the next standard rating

  • Ft = heat derating, Fa = altitude derating (the maker’s figures)

Design rules it applies

  • Its current, breaker, cable, ATS and fuel worked out
  • Put on the board it feeds and drawn in the single line through an ATS
  • The calculation as a PDF report

For reference. MO.tool works these out to help your design; the engineer remains responsible for it. Always check the edition of each standard your project uses and the requirements of the local authority (DEWA, ADDC, Civil Defence…).