Standards and regulations
- NFPA 72National Fire Alarm and Signaling Code
Detector spacing, manual call points, notification appliances and installation notes.
- BS 5839-1Fire detection and fire alarm systems for buildings (non-domestic premises)
The BS option of the installation details and notes.
- BS 7671Requirements for Electrical Installations (IET Wiring Regulations)
Saddle spacing (Table 4A) in the BS details.
- NEC 358.30EMT securing and supporting
Straps within 900 mm of every box, 3 m apart at most (NFPA / NEC details).
Design rules it applies
- Choose NFPA or BS: the notes and the cable change with it
- BS: detectors not within 500 mm of a wall nor 1 m of an air inlet; call points at 1.4 m
- NFPA: detectors 100 mm from a wall, 914 mm from supply diffusers; pull stations 1070 – 1220 mm
For reference. MO.tool works these out to help your design; the engineer remains responsible for it. Always check the edition of each standard your project uses and the requirements of the local authority (DEWA, ADDC, Civil Defence…).