Speaker current
I = P(tap) / V(line)
- V(line) = 100 V (or 70 V)
Public address (or voice alarm): zones, numbering, the 100 V line check and the schematic.
Speaker spacing, A/B circuits and the voice alarm (PAVA) link to the fire alarm.
The copper core resistance (Ω/km at 20 °C) for the loop and 100 V line checks.
The voice alarm’s cable note (PH120).
I = P(tap) / V(line)
Vk = V − Σ I(i) × (2 × r / 1000) × min(L(i), L(k))
ΔL = 20 × log10(Vk / V) ≤ 1 dB
For reference. MO.tool works these out to help your design; the engineer remains responsible for it. Always check the edition of each standard your project uses and the requirements of the local authority (DEWA, ADDC, Civil Defence…).